Dry type air cooling transformer is 1 phase 5000VA, H class enameled copper wire or aluminum wire, transforms 380 volt to 230/120 volt, input/output voltages can be customized as your need, just confirm us when place the order.
Share
Excellent quality industrial control transformer with 5kVA power rating, suitable for AC 50/60Hz, is designed to step down single phase 380V AC primary to 230/120V dual secondary.
Specifications
| Product Name | Single phase control transformer |
| Product Model | RELI-T-BK5000VA |
| Winding Material* | Enameled copper wire or enameled aluminum wire (Optional) |
| Total Output Capacity | 5000VA |
| Note: (If your output includes multiple voltage levels, please email us with the capacity of each output. The total capacity should be the sum of all individual outputs. For example, if your outputs are aV and bV, then aV (capacity) + bV (capacity) = 5000VA). | |
| Primary Voltage* (VAC) | 110, 120, 208, 220, 230, 240, 380, 400, 480, 110/220, 120/240, 240/480…(Optional and Customized) |
| Secondary Voltage* (VAC) | 6, 12, 24, 36, 48, 110/48, 120/24, 208/36, 220/48, 230/36, 240/120, 120/24/12, 110/36/24, 127/36/6, 208/48/36/24…(Optional and Customized) |
| Frequency | 50 / 60Hz |
| Insulation Level | F / H |
| Withstand Voltage Test | Primary to secondary 2.5KV/min |
| Primary to safety ground 2.5KV/min | |
| Secondary to safety ground 1.5KV/min | |
| Insulation Resistance | Primary to secondary 2500V>100 megohm |
| Primary to safety ground 2500V>100 megohm | |
| Secondary to safety ground 1500V>100 megohm | |
| Induction Withstand Voltage Test | 125Hz/ 800V/min |
| Ground Resistance | 25A<80 milliohm |
| Cooling Method | Natural or air cooling |
| Transformation Ratio | <3% |
| Air Carrying Current | <6% |
| Impedance Voltage | about 6% |
| Total Losses | 0.1 |
| Efficiency | 80%~99% |
| Operating Temperature | -25℃~40℃ (40℃, 93% RH, 56 days) |
| Storage Temperature | -25℃~100℃ (40℃, 93% RH, 56 days) |
| Certificate | CE, ISO |
| Warranty | 12 months |
| Size | Overall size: 240*180*230mm, Hold distance for installation: 180*160mm, Installation hold: 20*10mm |
| Weight | 46kg |
Schematic diagram illustration

Control transformer dimension

| Overall size (mm) | Hole distance for installation (mm) | Installation hole (mm) | |||
| B | E | D | A | C | K x J |
| 240 | 180 | 230 | 180 | 160 | 20 x 10 |
| Weight | 46 kg |
|---|